WHICH INSTRUMENT USED TO CALIBRATE CONTROL VALVE?
Answer Posted / v.suresh kumar instrumentation
The calibrate the control valve used for mA Source
Meter .mA Souce apply for I/P Converter so Opening Closed
for Control Valve .At the opening closed time measured for
position note.Supposed opening for Valve positioner 50% ma
13.5 So adjust the Zero or Span Calibration to Control the
ositioner
Chart
% Actual Value Error Zero/Span
0 4.7mA 0.7 4mA
25 8.5mA 0.5 8mA
50 12.0mA 0.0 12mA
75 16.4mA 0.4 16mA
100 20.5mA 0.5 20mA
| Is This Answer Correct ? | 81 Yes | 8 No |
Post New Answer View All Answers
TECHNICAL/ARTITUDE
How to calculate P,I&D value in PID controller ?
What is the constant voltage unit?
how can i check vortex shedder bar it is ok? if there is ohms condition are shown correct?
the whole paper was based on Transducers..questions like define repeatability, error,accuracy,precision..den there were many q. on the conversion of Pa to mmHg and other units.. also..der wer few Q. on some level sensors(with diagram)
What is first echo & echo window in radar type level transmitter?
PLEASE PROVIDE SAMPLES OF CHEVRON SKILL TESTS
How digital input and digital output 's are working in dcs
why using negative supply for bentley nevada vibration system ?
May I have a brief note above the voltage barriers? Whats is the purpose? Please mail me if you've operational details, mail id: rajkumar.diice@gmail.com
what is the procedure to callibrate temp controller ,pressure controller,etc. suppose a temp controller showing error 1.5 degree centigrate how can i minimize it.
can anyone tel the syllabus or previous year question paper for BHAVINI(EIE)2014.
Why we are using DPT(Differential Pressure Transmitter) in separator instead of level trasmitter?
flow transmitter formula?
what are the selections available in configuring a burnout protection of a controller? thanks