if 50hz transformer is required to be run on 50% frequency
what needs to be done???????????
Answer Posted / ashokreddyreguri
flux is proportional to E\f or V\f
if the frequency is reduced the ratio V\f will increase so
flux will increase.so to maintain this flux magnetizing
current required will increase.this reduces the no load
power factor , so on load power factor is also reduced.
this also reduces o\p of transformer.so V/f ratio of t/f
must be maintained constant.
as 50% of frequency is applied to maintain constant V/f
input voltage applied must be 50%if rated voltage
| Is This Answer Correct ? | 16 Yes | 0 No |
Post New Answer View All Answers
why T/F winding temp measurement cts are odd secondary current ie,109A/1.2A/1.4A?
What Is Connection APFC Panel In Compony.
what is Insulation monitoring device. where it is used? (in switchgear room or control panel or in field equipment)
Why does inductive loads consume KVARs?
What is difference between start imitation and start interlock for 3 phase motor protection ?
What are the different losses In a de mac1une'! t.xplam
A 100KVA SINGLE PHASE TRANSFORMER 10000/200V,50HZ REQUIRES 300V AT HV SIDE TO CIRCULATE FULL LOAD CURRENT WITH LV SHORT CIRCUITED.THE INTAKE IS 1000W.THE % OF REGULATION ON FULL LOAD AT 0.8 PF LAGGING WILL BE HOW MUCH AND THE SECONDARY TERMINAL VOLTAGE ON 0.8 PF LEADING WILL BE
I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?
in electrical control panel. how can i choose the cable rating. (example - 11kw motor, 18-25A mpcb}
in cvt,there are two windings,1a,1n and 2a,2n.in my one project i use only one winding i.e.1a,1n. the other winding is not in use, so i connect it in open delta and want to close it by ibsertibg thermal resistor. the output of cvt is 132kv/115/sqrt3. plesae tell me exact value of resistor, so i may close it to avoid the resonance phenomenin. send me answer on this email adress please. aetcon-po@aetcon.com
What is the equivalent circuit of a transformer and its vector diagram?
What do you mean by Frame 5 Gas Turbine as well as Mark II.
write down the formula of cable size in RM if current is 50Amp.
how to test YNyn0 vector group in transformer?
What happened when capacitor connect series in ac circuit?