how to find motor contactor rating and bimetalic relay
rating? of 30kw motor which will operate on star-delta
starter?
Answer Posted / elangovan t
You can use Type2 coordination table to find out the
contactor rating and OLR rating.
Normally the OLR should be set at the Full load current
rating of the motor. Hence the OLR may be selected such that
the motor flc lie in the mid range of the relay span
| Is This Answer Correct ? | 17 Yes | 2 No |
Post New Answer View All Answers
In between UPS out going changer over switch and ups raising main input, both side cable gland producing heat but the cable doesn't get heat,Why?
A logic circuit that provides a HIGH output if one input or the other input, but not both, is HIGH, is a(n)?
What are the two types of compensation?
Why does amplifier gain reduce?
All tape of electrical questions Answers tape of motor transformer e.o.t crane
What is load boxes ?
In EHV transmission line a neutral grounding reactor is often placed at neutral point of shunt reactors. What is the recommended protection for this neutral grounding reactor? Should I use a fast closing switch to bypass neutral grounding reactor when this protection operates?
how to apply b license to c license in tneb
how does the rotating m.m.f is produced in the 3-phase induction motor and how the poles are created in 3-phase induction motor ?
for 4 MVA , 33K.V/6.6K.V transformer. secondary side the connected load is 3000H.P. What is the rating of capacitor bank to be insttaled.
why ups rating in kva? and why ups are in parellel?.why isolation transformer is used in ups?
Why AC current leads voltage in capacitor and how?
Define the term factor of inertia.
temp of cast resin 1500kva tx formerwent up to 138.c but came down very fast to about 100.c within 20 mins when load was reduced from 70% to 60%
plz send me HPCL apptitude paper.. maulik_elect@yahoo.co.in