if generator is running in iso mode parrallel with grid and
suddenly grid breaker off what will happen?
Answer Posted / blake australia
If generator is running in ISOC mode (opposed to base
loading) and the grid connection is lost the generator will
try to pick up the load on the connected network. If the
load is too big then the generator will trip. If the load
isn't the generator will continue to run as before. ISOC
mode means that the generator is running in its own
frequency control, so if it looses the grid frequency it
can still run based on its own frequency.
If the generator was running in base load and the breaker
trips the generator will have no frequency reference.
Usually they are configured to change themselves back into
isoc when grid reference is lost but you should check if
unsure.
| Is This Answer Correct ? | 17 Yes | 1 No |
Post New Answer View All Answers
plz send me Bhel, Mahagenco, sbi previous exam paper for electrical engineer on my email-id kambali_smita@yahoo.co.in
how much winding resistance of 0.75kw to 12.5kw 3ph sqwiralcage induction motor?
List out the different frequency domain specifications?
what is the relation between reactive power and power factor for the what is the limit of reactive power and power factor
What are the specifications for getting approval of Substation?
ii) A shunt motor supplied at 230V, runs at 900 rpm when the current is 30A. The resistance of the armature is 0.4 ohms. Calculate the resistance required in series with the armature to reduce the speed to 600 rpm, assuming that the armature current is then 20A. [12]
EXPLAIN THE WORKING OF SERIES REACTOR IN HT CAPACITOR BANKS (FOR VOLTAGES & CURRENTS)
What do you mean by turns ratio of instrument transformer?
How can we measure earthing resistance test (Earth meggar) of Transformer neutral pit while in live condition?.
is the value of inductance depends upon the value of thitha in doubly excited machine??
What is the use of mc( moving coil) in dc voltmeter and dc ammter and what is the use of ( moving iron)in ac voltmeter nd ac ammeter
In control room of our one plant there is a continuously the incoming power goes to PC is vary,means in stabilizer it continuously indicate from high input to low and low input to high. what is the reason and its solution.
what is V.L.F. testing of power cable? do you know the voltage ratings, like for what rating and size of cable what rating of V.L.F. testing is used?
what is meant by surge? what we called for high currents?
what are the ''pitting rings''and how cn they be controlled in a series generator