If the capacitor bank is installed in switchyard say
132/22kv then on LT side say 22kv/0.433kv is it necessary to
install capacitor bank for maintaining power factor. if pf
is maintained on HT side then will that be maintained on LT
side as well.if not then how&why??????/ please
explain...........

Answer Posted / vijaykumarht

The capacitor bank on HT side will anyhow correct the PF,
the line losses will not be reduced. hence by putting the
capacitors on LT side, that too nearer to the load, the
losses and PF can be much better improved. The capacitors on
HT side is just to minimize the line losses, even though it
improves PF putting capacitors on LT side is always
recommended that too nearer to load, so as to get efficient
usage of electricity.
Please not that this answer is only for inductive load
consideration as linelosses and transformers and most of the
loads conneted to the line is inductive.

Is This Answer Correct ?    23 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

At what factor resistance r of a conductor depends?

643


how does an centrifugal and screw type chiller will work. which chiller efficiency is high and why.

1843


What is the distance between body earthing and neutral earthing.?

4112


when will be the iocl interview results i faced interview on 8th september 2008 iam from electrical branch i faced interview for the post of electrical engineer??????????????????????//

1590


what is meant by flywheel and its role in retardation test

1968






What is control system?

731


what is meaning of 230volts ac 50hzs ac supply is it rms or maximum to getting ac 230v what amount of max voltage they will send

1551


there is an alternator 480 k.w, 400v,50hz, 4-wire running on load having leakage alternator body earthed current 38 A. is it within acceptable limit? if yes then give reference if no then how to bring within specified limit

1501


What is vaccum currcuit breaker.define with cause and where be use it device?

636


WHAT ARE THE DISADTAGES OF SINGLE-WIRE-EARTH-RETURN SYSTEM USED FOR RURAL ELECTRIFICATION?

1489


How to work definite,over pluxing,revers power,OSR relay

1252


is ac supply can store

1520


What is the difference between rulling span and wind span of of an Over Head Transmission Line?

1845


The power factor of the fixed load is 0.8, now the p.f is varying from 0.8 to 0.5.

1579


how we can calculate chiller required ampear?

1596