why transformer ratings in kva?

Answer Posted / suresh

kVA is the unit for apparent power. Apparent power consists
of reactive and active power. Active power is the share of
the apparent power which transmits energy from the source
(generator) to the user. Reactive power is the share of the
apparent power which represents a useless oscillation of
energy from the source to the user and back again. It
occurs when on account of some »inertia« in the system
there is a phase shift between voltage and current. This
means that the current does not change polarity synchronous
with the voltage. But the heat generated in a winding as
well as the eddy current losses generated in a transformer
core depend on the current only, regardless of whether it
aligns with the voltage or not. Therefore the heat is
always proportional to the square of the current amplitude,
irrespective of the phase angle (the shift between voltage
and current). So a transformer has to be rated (and
selected) by apparent power.

Is This Answer Correct ?    14 Yes 10 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Whats the difference btwn a latch, port,data bus buffer? Do they all not hold data in d flip flops??

1967


how to calculate magnetic force genrated by a coil ?

1739


what is dry and wet frequency withstand voltage? why & where it is used??

1781


How the PF control while running DG set with load

1631


why induction motors are rated at 0.8 power factor.

1535






How RTCC panel is working and give single line diagram for RTCC with transformer?

2650


1. What is the exact formula for one weber? for example,(one ampere = one coulomb electron of electrons crossing a point of conductor at one second. i.e, 1A=1Q/1sec)

1423


Diagram on interconnectivity of 11kv transformer with RMU (i.e, one incoming and two outgoing or two incoming and one outgoing)

2221


what's the difference between 'shaft power demand' and 'BHP' , when we consider electrical load list.

1089


i am an maintenance engineer. one distribution board have 5 feeder. recently its ELR trips frequently, but it take some times after trip( 10min,20min..)but 3 feeder no load. two feeder only loaded. i checked one feeder IR value all values are above 50Mohm.but B phase to Earth is only 9Mohm.any problem about low value

1421


What is accuracy of a measurement?

723


my bachelors was done with EEE now i got admit in NU with CS as course. how to answer this qns 1) why u choose cs? 2) why u changed from eee to cs

1281


1.ZEBRA conductor(large size) 2.KUNDHA conductor( small size ) 3.panther conductor(very small ) 4.lepard conductor (very very small)

2449


how can i determine the gear ratio for a rack and pinion system if an electronic gate operated by an electric motor is to travel a distance of 5meters in 15 seconds.

1633


Please explain me abt PQ diagaram in the power sector.

1927