why in three phase 440 circuit in all phase current is
almost equal L1-35 A,L2-34 A ,L3-31 A but in nutral when i
check with clamp meter it shows 25 A?
Answer Posted / kiran
Principle is vector summation.
Ir + Iy + Ib = 0
and not arithmatic summation.
Since neutral current is substantial 25A, the three RYB
vectors are not 120 degree apart. Means powewr factor in
each phase differs drastically. Thats why though there is
no much difference in RYB current, neutral has substantial
current.
Is This Answer Correct ? | 18 Yes | 2 No |
Post New Answer View All Answers
Draw the DOL starter and star delta starter drawing?
If a transformer primary winding operates at 240v, the secondary at 120v and the load is 1500w & the transformer is rated at 92% efficient, what's the current flowing through the primary winding of the transformer? What is the formula for finding this?
explain PV modules in solar energy generation.
What is the HVDC Transmission System? What are the conditions applicable to lay an HVDC Line?
why occ characteristics of generator is also called as magnatization characteristics ?
At what speed 1 HP motor can run an electric car of weighing 400 kg?
What is critical disruptive voltage?
What is the exact formula for one weber of magnetic flux?
why and how current drawn by battery charger depends upon the altitude where it is located?
given data are load current & power factor cable core size? plz any one update the calculation formula
Describe the control mechanism of missile launcher???
DG cranking voltage?
List few applications of d.c series motor?
Why the dc voltage drop during starting of emergency lube oil pump? The Voltage drop from 135kv to 125 kv for one min. before re-establish to 135kv?
What kind of preventive maintenance are there for transformer?