The coils having selfinductancs 10mh and15mh,effective inductance 40mh when connected in series aiding. what will be the equivalent inductance if we connect them in series opposing?
Answer Posted / sethu
L = L1 + L2 ± 2M.
When ordinary, L = L1 + L2 + 2M
∴ 40 = 10 + 15 + 2M.
∴ 2M = 15 mH
When opposing, L = L1 + L2 – 2M
= 10 + 15 – 15 = 10 mH
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
how many load we can take for lighting
In cable sizing calculation (determining the max route length of cable) why we choose the shortest length between cable length of full load current Iflc & starting current Istart?
sir i ve applied for hindustan petroleum and power grid india ltd..and the exams on feb 22.can you pls send model papers and tell how to prepare for those.i need to get into any of these for sure.....
What is meant by turbo alternators?
a simple c++ program to calculate simple interst with its data members as private
which type of effect of turbine and generator reverse power protection ?
Why do we use center tap transformer that used with portable tools
Is better to supply the voltage for static exciter from the auxiliary power source or from the SG terminals? And why?
Why do power lines not short out when they fall into water?
What si the d/f b/w KVA & KWH, kvarh & kvar, kwh & kvar phase voltage & line voltage
In convertor can we use rectifier thyristor in place of invertor thyristor with explain.
Electronic circuit
What is the formula for selecting the cabels according to load? How to calculate what sq.mm cabel to be used?
why moisture formation found in XLPE Armoured cable outer sheath
Sir 33kva 2 transformer load 900 amp calc 1800 amp mana jayega