How to calibrate vertex flow meter?
How to calibrate mass flow meter?

Answer Posted / jigaranadkat

Vortex:

Practically it is a volumeteric flow measuring device and it is not possible to calibrate online in field in most of the cases (Provide you have a proper bypass arrangement and proovers in place) , hence it is to be sent to calibration LAB where it will be compared with MASTER meter.

This MASTER meter must have superior accuracy than UUC (Unit Under Calibration).
Usually the large volume flow is tough to establish at calibration LAB hence Gravymeteric method is used in which water is passed through UUC and compared with high accuracy Load-cell. Since water density is known and constant, volume flow is calculated and new K-factor of meter is calculated.

Mass-flowmeter / Coriolis meter : Same Above mentioned Gravymeteric method is used.

Hope this will help ..!!!

Jigar Anadkat

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

hello sir/madam, I,Subramanian need 5yrs placement papers of officer trainee of Instrumentation technology.pls send to this mail id mani_nxtgen@yahoo.co.in please do the needful. with regards, subramanian.v

1773


how to connect transmitter measuring sulfur process? 1-by using long impulse line or 2- by using coated short impulse line

1585


Describe the function of Accumulator into the Pump

1488


why we use impulse line of flow transmitter at 45 deg. angle both side of orifice plate.

1946


i need some objective type questions in instrumentation

4485






Explain why use mmwc unit?

640


Which is your favourite subject & explain any one topic of it.

9000


Why humidity limit is 30 to 55 % for raw material storage?

3622


WHAT IS TMXT IN TEMPERATURE FOUNDATION FIELDBUS.

1874


What is feed factor and its Importance in cement industry? How we can solve feed factor?.

3096


How will you calibrate PID controller? explain with example.

1977


How addressable fire systems work? Pl. send details with architect.(Loop), also send details regarding Gas system. Pl. help me.Thanks

1643


in natural gas indirect water bath heater,how to prevent the problem of backfire from firetube during ignition...becoz of this backfire performance of wbh is going low.

2297


Can anybody tell me which type of question are asked in the interview for the FORMULATION(Pharma) as a instrumentation engineer, & question in building managment system.

1589


Hook up resistance decade box to temp.transmitter.

1726