How can I make calculation for Install level transmitter
(DP) for open tank and cloes tank?
Answer Posted / mnb
For open tank you just connect HP side to the bottom of the tank and vent LP side to the atmosphere.
Head pressure becomes liquid level .URV=Height*specific gravity (H*SG) and LRV =0.
For closed tank, use dry leg for non condensate liquids and use wet leg for condensate liquids.
Dry leg-connect HP side to bottom and LP side to top of the tank. LRV =0, URV= H*SG.
No need to bother about pressure inside the tank because it acts upon both sides equally.
Wet leg- connect Hp side to lower tapping and LP side to upper tapping and fill the Lp side with process liquid.
LRV=h2*sg
URV= h1*sg-h2*sg.
h1= level of liquid at HP side
h2= level of liquid at LP side.
Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
1. For Steam drum level signal, why do we compensate with drum pressure signal? 2.For main steam Flow signal is comensated with main steam temperature signal and main steam pressure signal why?
, Instrument Index, P&ID review, I/O schedule, datasheet, DCS / Analyzers specifications, loop diagrams, hook-up drawings.
what is the input of digital counter during the the calibration time?
Where is wet leg is used?
how to calibrate steam control valve in steam turbine
How to calibrate radar type level transmitter for interface level? Total liquid(liq.1 and liq.2), level both the liq individually? For. Both the liquid levels how the signal will go from transmitter to dcs? How to calibrate. Single radar 9:26:55 AM for 2 different liquids in a tank?
What is Droop? What is Step/Gradient Limiter in Turbine Governor control?
flow transmeter accuracy 0.075% of full scale & find ucertainty is 0.025 % so what is maximum limit band of uncertainty
all types of liquid analyzer principle with drawing?
plz tell me clearly about PID.."when v have to change I value,D value,GAIN??
please send the sample qustion paper for iocl written test ..
How to find out the current of two motors having same power consumption but different RPM?
our kks tagging is crossing more than 12 character please suggest how to take tags in the DCS
i have done DAE in Instrumentation and Process Control. i have applied for an apprentice training in chemical company after three day my interview will be conduct but i need more information about industrial process control and controller. my e mail is imran_dilsetu@yahoo.com please tell me interview question relative to instrumentation ?
Name different types of bourdon tubes.