how we convert Mili ampere
to temp txt,level txt,flow txt,pressure txt range value

Answer Posted / abdul rauf

Actual formula is PV (procees variable)-LRV/Span×100%
Range=l2-4/16×16
=50%
And process Varible (ma)=Rang in % ×Span/100+LRV
Ma=50×16/100+4
ma=12

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

When doing a liquid seal on a differential flow transmitter , most of the time the sealing liquid will be heavier then the process fluid. For wich application will the sealing liquid be lighter than the process fluid if transmitter is mounted below the process line.

1399


How flow can be measured with dp?

673


If we increase only P what will be controller action ?

1631


I am using 971 Enraf radar level transmitter for LPG tanks ,the tank side indicator gives the error code 999999999FL can any body give me any diagnostic for this issue?

1768


Why the ammonia and Nitric Acid level indicators is with millimeter ? and What is the conversion form millimeters that level indicator indicate to weight ?

1211






NPN transistor, SCR, Zener diode, LED, Varactor diode, Vortex meter, RTD, Resistor, Crystal

1742


Specific gravity.

1472


What are different types of orifice plates? State their uses.

635


how do calibrate the valves.. with clear manual

1551


please send the drdo exam paper

1952


what is wave length were using ?

1478


Calculate the maximum pressure drop that can be allowed to occur across a control valve, so that we can prevent cavitation / flashing from occurring. Use the following formula: Δ P allow = Km (P1 – PvapourA) where, Δ P allow - the maximum allowable differential pressure for sizing purposes, or terminal pressure drop; Km- the valve recovery coefficient from the manufacturer’s catalogue; P1 - absolute inlet fluid pressure; PvapourA - absolute fluid vapour pressure at the inlet temperature; Use Atmospheric pressure = 101.3 kPa, P1 = 1200 kPa(g), PvapourA = 4 kPa, KM = 0.72

1650


how to calculate signal cable sizing? and multipair cable sizing??explain in brief?

1899


I was working on calibrating turbidity transmitters endress+hauser at effluent polishing plant.We calibrated using NTU buffers.What happened is that when we immersed the sensor, everytime we raise and lower the sensor gradually, the reading will vary.my question is that is there any specifications on what is the required distance from the bottom of the container with buffer to the face of the sensor?Is it ok to install the sensor in a medium which has turbulence specially if bubbles are present?

1730


What is standard procedure of manual mapping in Radar type level transmitter?

1424