I have 320 Kva DG Set his KWh running is 77 , how i can calculate into electrical unit .

Answer Posted / tapas

KWH is always a consumption. Means its the difference of running value to previous value for a particular time period.

If here consumption is 77 KWH in 2 hours then KW=KWH/Hr

KW= 77/2= 38.5 KW

So for KWH time period should be mentioned.

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

How to select transmission line type (i.e. 11kv or 33kv) for new established industries

1603


What is the function of auadag in a cro?

684


What type of core material is used for metering C.T and protection C.T???

1692


How can we calculate the transformer rating if the load calculated is 1000KW (11Kv Supply)?

661


What we mean by vintage of an engine+Generator?

1603






how can service sitting be setted for MCCB?Example for sittings IR (CURRENT RATING),IS(CURRENT STARTING)IO (current operating)?

1691


we use capister for power factor. when we use capaciter in dg circuit  than defect dg. can we use capaciter bank for dg circuit

1431


sir iam a 3rd yr eee student.no core company comes for recruitment to our college.my aim is to be placed in l and t.tell me the procedures.

1516


How to distinguish whether MCB is DC or AC looking at it physically

1538


if 2 coil of 1000W connect in series and 200 v is applied across it . then what is the total power of coil when coil have only resistive load .

1539


Dear friends I want to design busbar for1600 kva transformer(i.e2100 amps) what are all the factors to be considered before selectinga busbar what are all the standard sizes of busbars what is the formula for finding current of copper and aluminium busbar

1488


Why power factor should not be in leading (capacitive) mode of any load.

5868


EXPLAIN METOD OF IMAGE OF TRANSMISSION LINE/ WHAT ARE ITS PRACTICAL APPLICATION?

1425


what is through fault?

1770


why connecting surge unit in contactor coil

1387