I have one problem for masoneilan displacer type LT.I give some imformation in data shéet given for liquid level range 0 to 600 mm and sg .955 problem is 0% is ok 25%(23%) or 50%(48%)and 75%(73%) and 100% is ok this is up value and down value all ok so please halpe me

Answer Posted / rijesh

i hope that your calibration liquid you using is water[sg=1]. and your service sg=0.955.if so it is give you the output as per your observation
please make your calibration sg and service sg same value.
if you using service sg =0.95 and you using water for a measurement your maximuma span will be 95% and accordingly step change will effect.

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Meaning of the following a. IOP- Manimum; b. IOP- Maximu,;

1653


How it the difference between force balance system and dispalacement balance system?

1592


plz tell me clearly about PID.."when v have to change I value,D value,GAIN??

1682


Please can anybody help for control valve sizing step by step procedure?

1632


NSV type probe stands for

1961






How to erection of DCS Panel at site step by step

989


how many type of plug are used in pneumatic control valve,name them.

4348


What is cut off relay? And why use in PLC and DCS?

940


How is automatic reference junction compensation carried out in temperature recorders?

635


while am calibrating Drager polytron 2IR flame gas detector occured non zero status.how can i get zero status?

1700


I am using 971 Enraf radar level transmitter for LPG tanks ,the tank side indicator gives the error code 999999999FL can any body give me any diagnostic for this issue?

1751


Explain the burnout feature.

597


Why grounding is necessary? Give example with diagram.

1747


if in a level tx height is given, how u calculate the ranges of the tx?

6379


How can a d.p. Transmitter be calibrated?

678