PLease anyone can tell me CTUM-15 specification?
Answer Posted / neoveyron
CTUM 15 is a alstom make electromechanical relay used for the Sensitive earth fault protection for feeders by means of a CBCT. These operate on the principle of leakage current measurement by means of a residual connection of CT or a CBCT. These can be set for 1% to 16 % of CT ratings. The time dial settings can be set from 60 milliseconds to 750 miliseconds. These provide protection against high resistance ground faults on an earthed system.
Is This Answer Correct ? | 7 Yes | 1 No |
Post New Answer View All Answers
How Diesel Generator start ?
How calculated single phase induction motor req. Capacitor?
what is diff. between earthing grid,earthing mess, earting grid?
why would amp draw on neutral wire be as much as amp draw on the hot leg.
state the working principle of incondenscent tube?
What is the tests required for a 132 kV, 400 kV , 765 kV for a Circuit Breaker and Power Transformer before commissioning ?
What is the difference between diode and a transistor in terms of the direction of current flow?
If ROC does not lies inside unit circle,then ? a) Fourier transform converges b) Z transform converges c) Hatly transform converges d) Colpit Transform converges.
what is EIB lighting control system? what is the advantages of this system?
what are the Alarm, Trip & Safety equipment (Issues) present in Power Transformers pls Mail it to ashokbabunhce@gmail.com
Why Utility Distribution System in India is mainly at 11 kV? Why not Utility go for 33 kV?
What will be in Mahagenco Trade Test Exam? I want to know the same.
What kind of Neutral CT can be placed in 11/0.433KV transformer to be used and what are its specification?
what is capacitor voltage transformer?? how it is different from potential transformer?