i have a motor 55kw how u will calculate cable specification for this motor
Answer Posted / akhtar
If Motor is three phase:
we calculate the current of the motor?
Current(I)=Power(P)/1.73*cos fai* votage(V)
I=55*1000/1.73*.8*440
I=95.62A
now we can select the cable from catalogue
Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
HOW MUCH CURRENT DOES SYNCHRONOUS MOTOR TAKES AT SYNCHRONOUS SPEED IN NO LOAD CONDITION ?
Difference between ac parallel circuit and ac series circuit?
what is fault level of power system ?
A commercial Building is designed with 14th floor levels with indoor substation of three phase transformer with rated capacity of 1000 Kva.The transformer delivered 65% of its rated capacity at 0.67 power factor lagging.Because of low power factor, the power customer was penalized and certain cost was charged accordingly based on every point percentage lower than 85%.This situation may repeatedly happen on the succeding energy bills of power customer.The power customer is desired to improve its historical power factor of 0.67 lagging and no further penalty be impose by the local power company on the next bill. Q: Identify the appropriate solution you want to offer to Client?.Justify SCIENTIFICALLY and MATHEMATICALLY the principles behind the solution.
I completed iti in2004 I was worked in A grade contractor can I get c licence
Why squirrel cage motor can only use with low starting loads ?
Why MCCB is Getting tripped sometimes when there is no load in the Midnight ?
What is the difference between a verilog task and a verilog function?
What is the basis for selecting Vk/2 or Vk/4 for REF and Differential protection of Transformer and What is the significance of magnetising current
bitumar
WHY THE DIMENSION OF TWO SAME RATED MACHINE IS DIFFERENT ?
what is the difference between an alternator and a synchronous motor
what is a composite error in current transformers, why occurs & in which it will occur i.e, either metering ct/ protection ct
What is the drawback of class b amplifier?
what is the minimum recommended leakage current of an earthed cable connected to the body or skid of an alternator