Answer Posted / mugil
Assuming 24 vdc I/O cards.
On a transistor output card Sourceing is PNP or Active High. This means that you connect the output to the + side of the load device and connect the other side to 0vdc. If the output Card is Sinking it is NPN or active low meaning that you would tie the + side of the device to 24vdc and the common would connect to the output card.
On input cards if the input card is a sourceing card you would use NPN sensors. The cards common connection would be to a +24vdc source and the device (sensor) would give a path to 0vdc. If the input card was sinking you would use PNP sensors. The sensor would be connected to the + 24vdc source and the output from the device would connect to the PLC input card which would have a common connection to 0vdc.
Is This Answer Correct ? | 0 Yes | 1 No |
Post New Answer View All Answers
TEMPERATURE VARIATION FOR FREQUENTLY.
If a control valve is hunting means means if we are giving 50% to the cv, the cv will open at 51% then slowly slwoly it will reaches 49% , so what to do for solve this problem. The cv is double acting and mounted for anti surge operation, it having 4 nos. volume booster, one sov, one positioner, etc..?
what is different between 2,3&4 wire rtd and how much maximum distance using plc to field.
what can of fault ofently come in vibration mesurement?
-/5A. What is the meaning and limitations of this in energy meter constant. It is a 3 phase LT Energy Meter. If this Energy Meter is connected through a CT of ratio 200/5 Amps, then what is the multiplying constant and how its will be calculated.
Why rdt and thermocouple both give different output .and one things more, how to generate ohm or mili volt plz mail me merajalam143545@yahoo.com
What is the difference between modbus,fieldbus & profibus
IN CONTROL VALVE SPECIFICATIONS GENERALLY TERM " DE- 200" ."DM -400"USED,, WHAT IS DE/ DM STANDS FOR?
Describe how to use megger to measure the earth resistance and insulation resistance
when placing a vent or drain hole on an orifice plate should you measure from the center of the bore up or down for the vent placement?
Why do you want to work here
What is zero elevation and zero suppression?
What is difference of fanuc alpha series 16i and 18i controller.also what is differnce betn TC and MC controller
What is the PLC configuration in Cement industry?
What is loop1 and loop2 in MTS LT?