why are set -10vdc in bently neveda vibration system.
Answer Posted / dharmendra borada
Dears,
Bently Nevada Probes having Supply of -24VDC Supply because of NPN Transister used, so Sensor has to work between 0 to -24 VDC Range.
if u see the Graph of it's Vibration charesteristics it will be Linear Between -2 VDC to -22 VDC range & Vibration belongs towards &/or away from the probe.
and we can't say Vibration of M/C will be in which direction happens.
So it is Better to select middle point of it's Range as we can't assume Vibration Direction.
That's y Average/Middle point of Linear Graph range(-2 VDC to -22VDC) is -10 VDC(to Give Justice to Probe.
That's the reason of -10VDC Gap Setting needed.
Dear's this is the Answer according to my Knowledge.
Thanks in Advance.
Regards,
Dharmendra Borad
Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
what does it mean an active front end in vfd plz explain it briefly
What is standard of DCS panel design?and what is step of DCS panel design?wiring and type of connector(screw or DB connector)
How to interfacing microcontroller with a DC motor
what is the input to be given in digital flow meter during the the calibration time?
What is difference between “Fault Tolerant” & “Fault avoidance” PLC? Application where these system s are used?
What are the materials available to prepare individually for competetive exams in Instrumentation field? Plz reply...
How digital input and digital output 's are working in dcs
What is the purpose of the analyzer in petrochemical plant?
Somebody tell me in what way i need to prepare for csio pgrpe(adv instrum eng)interview?what all the quest can i expect?
2. What is ultrasonic flowmeter?
how to calibrate 0- 150 psi presure gauge by dead weght tester
Dear Friends, we are planning to design Power distribution and Fiber optic in the same cabinet.Like Front side Fiber optic and Rear side Power distribution.Is it any possibility of problem occurs like interference etc? Your answer is highly appreciate.
Calibration procedure for Electro magnetic Flow meter
Describe the functions of the Operator Interface including the considerations related to alarming and display layout/configuration/layers.
Yokogawa CENTUMVP R6.09 unable to download to Engineering Station with ExaOPC R3.75
The issue is when I try to download the common project section to the Engineering Station (STN) from the HIS in System View, it is unable to connect. The error displayed is:
WARNING: Could not connect to equalize destination. (7001)
Retrying. Number of retries = 0/1
ERROR: LdXopsLoadMain: connect error 10060
ERROR: Processing terminated due to connection error. (7002)
Equalization end with errors. STN0149
---- ERROR = 2 WARNING = 1 ----
Background:
>Updated the ExaOPC software on the STN from 3.60 to 3.75
>STN operating system is Windows Server 2008 R2
>HIS operating system is Windows Server 2016 Stanard
Solutions attempted include:
>Ensuring all IP addresses are correct and all networked devices can be pinged.
>The ability to ping a device using its host name from another device (