What is passive connection of instrument in different type
of I/O module
Answer Posted / carl_ellis
What is passive connection of instrument in different type of I/O module?
What is passive connection of instrument in different type of I/O module?
The output of a field instrument or analyzer that makes a measurement and provides a conditioned, high level signal like 4-20mA is characterized as either active or passive.
An active output is powered internally by the instrument. These are 3 or 4 wire instruments with a separate power wire or wires.
A passive output requires a DC power supply in series with its output in order to excite or power the output. This done to
- limit field wiring to 2 wires
- reduce the likelihood of a ground loop due to difference in ground potential between the field instrument and the receiver.
So, a connection of a passive (2 wire, loop powered) device has to include connections to a DC power supply, observing correct polarity at the field device and the receiver's analog input.
Carl Ellis
Measure First
Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
How many ohms are required for proper earthing?
Instrument QA/Qc what is the project quality plan?conduit inspection RFI. which documents attache with package?
What are the charcterstics of a P&ID controller block for Governor speed raise or lower for a load sharing functionality between 4 Gas turbines in droop mode.
i have been asked by QAFCO to appear for interview for thy post of Instrument Designer(INTOOLS)..i m engineering graduate with 5 years exp. in design engineering.Will this job profile suit me??i need all ur help n suggestions for thy same?
If a warning lamp will operate with the ground circuit is bypassed with a jumper wire to ground, what should you check?
why we are using magnet for calibration of gas detector?
How servomotor controls throttle valve of TURBINE?
What is Span Error
how to do dynolab wind speed sensor loop test, how to simulate value,i have simulate mA 4-20mA but not responding in DCS faceplate, please kindly advice me any one.
we have a s-5 simense plc having op7 .recently on op7 showing error 1.plc not present 2. DB error frequently. can u have any solution . please send me.
Please any one can provide latest aptitude test,technical test and interview questions for tata consulting engineering (TCE) i need it asap thanks in advance
hii my name is sujith...i am preparing for HPVL GET 2010... so ,,,pls help me by send any previous questions or material to my site.....(Msujith_12@in.com) thank q
How RAL(Rotary air lock)works in cement industry?
plz tell me clearly about PID.."when v have to change I value,D value,GAIN??
Sir, I am working as a Instrument Engineer in Grasim Industries. Can any body provide question answer for interview purpose