How to connect another 24 volt dc power supply in circuit when previous power supply has become weak.what is the connection?

Answer Posted / carl_ellis

A second power supply is wired in parallel with the first, but redundant/parallel power supplies should be decoupled from each other with power diodes, where each diode is forward biased on the power supply (+) output with the diode (-) coupled in common to the load).

The diodes need to be rated to carry the full current load. If diodes are not used, a severe fault in one of the power supplies could cripple the output of the 2nd power supply.

The isolation diodes must be installed on a heatsink to maintain operating temperature at a safe level. The power dissipation on the diode is determined by the product of the current passing through the diode and its "on" diode voltage drop.

Some recommend the use of Schottky diodes rather than silicon diodes becaus Schottky diode has a lower voltage drop so it runs cooler.

There are commercial diode decoupling/isolation packages sold with appropriately sized heat sinks to keep the diodes within temperature spec.

Carl Ellis
Measure First

Is This Answer Correct ?    3 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Tell me the field calibration procedure step by step with diagram of pressure gauge, pressure switch, pressure transmitter, temperature switch, level switch, flow switch, flow transmitter.

2705


what is sliding spool valves?

1822


i have been asked by QAFCO to appear for interview for thy post of Instrument Designer(INTOOLS)..i m engineering graduate with 5 years exp. in design engineering.Will this job profile suit me??i need all ur help n suggestions for thy same?

1794


What is the right procedure for adjusting the gap voltage of bently nevada vibration sensor?

14394


how to calculate orifice sizing? and tell me if pipe size bet 50mm t0 200mm then we can use pipe flange??? and above 250mm pipe size should i use D & D/2 Flange? is it right or wrong?

1490






We Have Two Field bus Pressure Transmitters of Different Sensor Range (I.E One is of Lower range and Another is of Higher Range).Is same Process Line. My Question is Can i provide Saturation Limit to my field Bus Transmitter as We can provide Saturation current limit to HART Instruments. As During Low Pressure Both Working OK ,But During High Pressure, transmitter with Lower sensor range Goes to Fault mode as Beyond its Sensor Limit it can Measure, So may I provide Saturation point Some where to Suppress This Fault during High Pressure.

1138


why use 50% lel methane gas concentration for gas detector calibration instead of 60% lel gas concentration whereas the hi alarm set at 60% lel.

2200


I need to know steps to Calibration Valve Guard......

985


field bus transmitter calibration procedure tell me

1343


How many ohms are required for proper earthing?

639


Q- What are the application in which PNP transistor is preferred over NPN ?

2835


can you send remote seal interface level transmitter calculation steps for oil water saperator.

2159


what is interface level and how it is calibrate?

1764


What is the working principle of the magnetic meter?

627


find the kp ki kd from the transper function G(S)=29.44s+04707/1.5349s2+s

1457