Why 1-5 vdc a standard?
Answer Posted / carl_ellis
1-5Vdc is not a standard, it is a widely used convention for 4-20mA current loops.
A 250 ohm resistor drops a 1-5 Vdc voltage proportional to the 4-20mA current.
DCS analog inputs historically used 250 ohms for 4-20mA analog input resistance and over time that value has become quite common.
But I have seen 1 ohm, 4.7 ohms, 10 ohms, 12 ohms, 24.9 ohms, 50 ohms, 62.5 ohms, and 100 ohm resistances for 4-20mA current input.
Is This Answer Correct ? | 13 Yes | 2 No |
Post New Answer View All Answers
Where Can i take a SPI INtools training in Mumbai? In Rolta India Ltd to whom I should approach regarding of SPI INtools Training?
centrifugal compressor interlock? Tell me the parameter at which compressor will trip
WHAT IS THE DIFF. BETWEEN SKIN TEMPERATURE AND PASSES TEMPERATURE..?
why any measurement made interms of pressure is more accurate ? to be more precise most of the flow velocity is made interms of pressure and it is accurate. what is the reason behind pressure measurement being accurate ?
POSSITIVE PULSE IS APPLIED TO AN INVERTER INPUT.THE TIME FROM THE LEADING EDGE OF THE INPUT TO THE LEADING EDGE OF THE OUTPUT IS 10 ns. THE TIME FROM THE TRAILING EDGE OF THE INPUT TO THE TRYLING EDGE OF THE OUTPUT IS 8 ns. WHAT ARE THE VALUES OF tPLH and tPHL?
I m appointed as an automation trainee engineer in small firm in that I am only the one , my company give me a project on s7-200 as i m beginner I don't know how to program so please send me the helpful site so that I complete my project before deadline....please help me out in this critical situation.
Explain the combusion chamber
Where is wet leg is used?
Can u tell me the principle of the tc,rtd,level switch,pressure switch ,transmitter(pr flow level temp.),vibration...plz
Which tank weighing system is better to install (Accuracy point of view) 1) Tank weighing system with 3 load cell or 2) Tank weighing system with 4 Load cell
Why 4-20 amps is being used in instruments? Why cant we use any other range instead of 4-20 amps? Why only 4 amps is taken as lower limit and why 20 amps is taken as the higher limit?
can u plz send me technical questions asked in SCHNEIDER ELECTRICAL technical paper?
What is Predictive Maintenance
What is difference between “Fault Tolerant” & “Fault avoidance” PLC? Application where these system s are used?
Why mmwc unit is used?