in 11kv generators the neutral point is connected to earth via earth coil while in the 33 / 11 kv transformer the neutral point is connected to earth via earth resistor why?
Answer Posted / vikas
This is neutral earthing concept. Normally for the generators of higher ratings we connect neutral to ground through a coil (peter son coil) to reduce the heavy fault current if fault occurred in the generators (Ph-Ph to fault Ph-body fault etc). Same concept for the transformer also but resistance grounding is sufficient for the 33/11kv transformer.
Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
given data are load current & power factor cable core size? plz any one update the calculation formula
can someone explain that how the speed of the protection system affects the fault level calculation?
I WANT TO know WHICH WAY IS BETTER FOR CONNECTION BETWEEN POWER TRANSFORMER AND MAIN DISTRIBUTION PANEL. 1-IS BETTER WE USE CABLE? 2-IS BETTER WE USE BUS DUCT? my transformer rate power is 2500KVA
i need previous entrence exam papers of nhpc.
What is the power factor of a transformer at no load?
Why saturation region slowly shifted in the left side?
Metal covered multiconductor cables shall employ a marker tape located within the cable running for its complete length in lieu of cable surface marking. Is it true or false?
What is the best thing to protect the motor from running over full current. CT or O/L or pressure transducer at the given pressure rating
What are :- AC Distribution Board (Single & Double Front) DC Distribution Boards Distribution Board LT Breaker Panel.
How can a equal potential zone be carried out in conductors?
how to find the resistance and gap volatage of the diode??
relation between power station capacity and voltage level?
Define non-touching loop.
how does directional relay work incase of ac ?
All tape of electrical questions Answers tape of motor transformer e.o.t crane