what is the procedure to isolate flow a transmitter and
flushing it?
Answer Posted / abu khaled
1-close the high side valve from manifold
2- open the equalising valve
3- close the low side valve
4- close the equalising valve
5- be careful do not open the three valve in the same time
to avoid damage sensore or cabsoule .sometimes the prosses high temperture or cmical can damege cabsoule>
or maybe there is seale liqude in the high and low side
6- open the vent for low side to zerw check and be sure the equalier valve is closed .
7- if need calibration use high side connections
8- after being sure the TX is oky go to next step
9- make flashing to both sides high and low if they are blugged aske operator to isolate from orfice plate and aske piping group to flash tow lines
10-to return the TX to servse
11- open equalising
12- open the low side
13- close the equalsing
14- open the high side
| Is This Answer Correct ? | 8 Yes | 11 No |
Post New Answer View All Answers
Why upper weighing limit of electronics balance is 90% of the total weighing capacity?
How to calculate P,I&D value in PID controller ?
What is defferent betwen ESP &PCP PUMP .HOW IT IS WORK?
principle of automatic votage regulator
what are the values of fuel flow rate in various places in boiler.
What are advantages and disadvantage of the ac supply load cell?
How the sizing of the analog signal cable is calculate?
need instrumentation job completed 1 year trainee ship in mnc pesticide company. now in search of job
What is intrinsically safe system?
how many types of spped sensors n vibration sensors?their basic principle n connection?
what is the field bus calble ? what are diffrences in orang colur cable and black coular calble ?
model question paper of instrumentation for Jindal GET 2010.plz reply sudhanshukumar08@yahoo.com
What is frequency factor in massflow meter? When using frequency output?
why any measurement made interms of pressure is more accurate ? to be more precise most of the flow velocity is made interms of pressure and it is accurate. what is the reason behind pressure measurement being accurate ?
What is the function of solenoid valve in on/off & shutdown valve and why it is not used in control valve normally?