Dear Friends,
Need your help for connecting APFC panel,
Quotation : I have 2 No’s 1000 KVA Transformers, both transformers are having separate APFC panels, ( Tr-1,400KVAR, TR-2,450 KVAR)
Now I want to stop One transformer, present load is 650Amps, Max, So One transformer is enough, I have switched OFF TR-1, but PF is not maintaining properly, its 0.5, So now I want to connect TR-2 APFC also in TR-1 Loads, Can any one answer for my Quotation with drawing, how to connect TR-2 APFC panel in TR-1 Loads,
Answer Posted / moh
Please use a bus-coupler circuit breaker between the circuit breaker of TR1 and the circuit breaker TR2 with interlock (mechanical or electrical). When one TR is out the another TR will connect to another load and APFC by the bus -coupler circuit breaker
Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
what is the relationship between current&voltage in practical purpose ?
what is the difference between oil surge relay and buchholz relay.
how we can calculate chiller required ampear?
hi there i am highly enthusiastic about discussing electrical concepts , and hence i wud lyk to invit al do intrested to join me at gtalk and hav a dscussun of the concepts , ad me as a freind . my email id is rakesh.2k99@gmail.com
how we design a pannel to start 10HP motor with the help of star delta starter?
How equivalent impedance is calculated in thevenin theorem?
how technical is calculated in 11kv line and lt line
What is called limb of a transformer?
we have 3 single phase transformers. how will we generate 6 supply from 3 phase supply input
In parallel operation time both NGR’s close or not close if both close what will happen
bsec exam syllabus (mis)
How Can You Relate Power Engineering With Electrical Engineering?
What is domestic transformer? Draw the connection of domestic transformer.
Explain the terms real power, apparent power and reactive power for ac circuits and also the units used.
i am going to attaned the engineer (disign)iterview at HAL please give me duid line