If the kvar rating of capacitor bank is
600 kvar at 525V then what it's rating at
415v.
Answer Posted / ahamadkutty
THE MAXIMUM CURRENT RATING OF THE 600kVAR CAPCITOR IS
600000/525/1.7321= 660 AMPS.SO AT 415 VOLTS LIMITING THE
CURRENT TO 660 AMPS THE RATING WOULD BE 415x660*1.7321=
474.3kVAR
Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
How phase displacement change in the over current relay coils.
PLZ sent the previous year question paper for GET in NHPC on my EMail id ppshanker@gmail.com
What is the complete procedure of erection of electrical panel in industry
what is a bus riser in power system and why it is used
y we use neutral,all r told its used to for closed path..k its a just used to closed path,in a transmission line y we put same conductor used n both phase and neutral..if we use less than phase conductor in neutral mean we ll reduce cost its right r wrong..if we use mean any problem occur in transmission line..
can we use trip light with bus coupler?
Why 15Amp. MCB is suitable to carry load of 1.5Ton Ac please Explain?
tan delta equation test on alternators
can any one tell in easy method for circulating current ??
Give accurate definitions for these electric terms: Inductor Inductance Inductive Induction Reactance Reactive Esam Baraka ٢١ ساعة
how we can adjust for three phase motor cold stall time ,hot stall time and thermal register set up?
Write down the design procedure of commutaj.
I want to replace the 3 KW DC motor with AC motor so what should be the rating of AC motor? Details Of DC motor to be changed with AC are - Kw - 3, Vf - 310, If - 0.15, Va - 400, Ia - 13, RPM - 2400
When we need up only in o/p 440v, so why we use directly in 11kva in input?
Difference between megger test equipment and contact resistance meter test instruments?