A 200 KVA UPS's load current is 70 A. We want to provide a
Generator back up. What capacity of DG required for this ?
Answer Posted / laxmikant
Question is not clear,
Because 200kVA/(1.732x0.415kv)= 278.24 Amps/phase.
Please check. If you load demmand is 200kVA , as DG runs
always with 89% efficiency @ 100% load, You may choose for
250kVA DG.
Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
IF DISTANCE IS 100METERS B/W AMP.METER AND CURRENT TRANSFORMER WHAT WILL BE AFFECT IN ACCURACY .METER CAN SHOWING ACCURATE CURRENT OR NOT IF NOT WHAT CAN I DO TO GET 100% ACCURACY.
How much of the total hydro power potential has been exploited so far in india?
I am doing apprenticeship training at HT switch yard in NLC. How can i get electrical c license. ??? What r the rules for getting it as an apprentice? ??
What do you mean by reach and reach the point of the relay?
if we have a industrial load of 400 kilowatts with 415 volt AC then how much total harmonic distortion (thd%) should be acceptable for steady power system.
How to back charge the Gas turbine generator
hey guys help me out.....what are the industrial uses/functions of nozzles in industries
Zone of protection and tripping scheme of arc protection relay.
In control room of our one plant there is a continuously the incoming power goes to PC is vary,means in stabilizer it continuously indicate from high input to low and low input to high. what is the reason and its solution.
Why water bubbles when D.C. Current is passed through it? Why not when A.C. Current is passed?
What are the parameters of water ( Water quality )to be monitored in Centralised HVAC ( water cooler chillers )
importance of reactive power management
WHAT IS THE FUNCTION OF SHORT CIRCUIT MAINTENANCE CT
A parallel flow heat exchanger will perform better than a counter flow heat exchanger. State if the statement is true or false.
what is the difference between skin effect