If a control valve is hunting means means if we are giving
50% to the cv, the cv will open at 51% then slowly slwoly
it will reaches 49% , then it will reaches again 50%, this
type of action occured frequntly.. so what to do for solve
this problem. The possible cause is in volume booster or
positioner's relay.. positioner is double acting .. and
make siemens..sipart.The cv is double acting and mounted
for anti surge operation, it having 4 nos. volume booster,
one sov, one positioner, etc..?
Answer Posted / avinash d. pagar
Also please check volume booster function separately with
out positioner and then set factory setting of positioner.
again calibrate positioner by auto calibration. mostly
hunting and over shooting issues cause by booster error.
Is This Answer Correct ? | 4 Yes | 0 No |
Post New Answer View All Answers
what can of fault ofently come in vibration mesurement?
how is work pressure switch& level switch?what is the principle of this?
why is an oxygen sensor used in a boiler stack
How to calibrate displacer type level transmitter (chemtrol make )for level measurement in hotwell , LP & HP heater ?
Why do you want to work here
how to calibrate and troubleshooting of leveltroll?
What are advantages and disadvantage of the ac supply load cell?
What is ultrasonic flowmeter?
hi,i am doing 3 year in electronic and instrumentation engineering. what type of aptitude questions will be asked in a core industries and how can i improve my skills in instrumentation?
What types of Instrumentation Related Questions can an Interviewer ask in a Telephonic Interview ?
what is different between 2,3&4 wire rtd and how much maximum distance using plc to field.
How do bending tubing provide better measurement than using tubing fittings such as elbows?
if in a level tx height is given, how u calculate the ranges of the tx?
how works encoder in plc
Why not come out analog output in ABB EL3020 when display show correct value