I saw one P&ID 6" control valve has been connected with 8"
process line, and 2" valve also connected in parallel with
6" valve. why the 2" valve connected in parallel, Is there
any technical reason. please clarify. With Regards-Kittu
Answer Posted / girishkumar
It is called split range control and split a big CV into two
parts as 1:4 for fine control.ie:- in 0% both valves keep in
close. In 25% the 2" valve keeps fully open and 6" keeps
fully close. In 50% the 2" keeps fully open and 6"keeps in
25%open. In 75% the 2" keeps fully open and 6"keep 50% open
and in 100% both keeps fully open.These two valves
controlled by same controller with two AO.
Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
what is gas metering system? gas chromatograph? and gas compressors?
What is feed factor and its Importance in cement industry? How we can solve feed factor?.
How r the calculation of process line mpm.
Can anybody please let me know Orifice plate sizing calculation formula and step by step procedure
in sulfur process what is material of impulse line we use to connect with transmitter ? and does teflon affected by sulfur?
What is Cavitation in a control valve?
can any send me a forbes marshall dtron 316 manual
flow transmitter formula?
what is wave length were using ?
What is shielding effect?
Explain the working of rota meter.
1- Explain about HPM 2- What is the FSC and explain the configuration of FSC 3- explain the complete loop of vibration, how it works (field to control room) 4- What is the use of proxymitter? 5- During job your partner effected with H2S then what you have to do. 6- what type of gland packing uses when valve glind is leaking.
1.what is controller proportional gain 2.what is the controller intergral action time. 3.A proportional plus derivative controller that has a proportional band of 20% and a derivative action time of 0.1 minutes. Construct the shape of the output waveform for the triangular input if the input rises and falls at the rate of 4 units per minute.
what can of fault ofently come in vibration mesurement?
which type of signal used in instrument?