In a 3 phase,400v,4 wire system, 2 incandescent lamps, one
having 230v,100w and the other 230v,200w are connected between
r phase- neutral and y phase-neutral respectively. If neutral
wire breaks which lamp will fuse first and why?
Answer Posted / awdhesh
When neutral disconeted bulb are in series so ckt current is same but voltage drop is diffrent.vlt drop is propesanl to R so 100W lamp R is more with respect to 200W. 100 W lamp fuse first.
Is This Answer Correct ? | 36 Yes | 5 No |
Post New Answer View All Answers
why fractional pitch winding generally used in alternators?
what is the excess air in furnace
what is the working principle of energy saver control panel. please give the complete calculation & theory.
what is the effect of connecting three phase supply lines to three phase auto transformer output terminals through a fuse of 10Amp and a circuit breaker (MCB). Is this connection permanently destroy the transformer?
hi, i have 3x200KVA and 2 x 80KVA UPS with battery bank of 150AH 68Nos. and 100AH 204Nos., i need to install AC either ductable or PAC type, so can you help me to calculate heat load and capacity of the AC to install.
How to Calculate KA Rating of Main LT Panel
what things to be considered when designing UPS
What types of CMOS memories have you designed? What were their size? Speed? Configuration Process technology?
sir i am apearing for nic exam.i dont know exam pattern.can you please send me some model papers
Can Anyone suggest the Standards (IEC or IS) for selecting copper current density?
What is center gravity load in substation?
Why is back emf used for a DC motor? Highlight its significance.
what will happen if earth of 33 kv cable (earthed system) is not connected to earthing pit?
send me all basic electrical question and answers
how we can adjust for three phase motor cold stall time ,hot stall time and thermal register set up?