Hi frnds :)
plz tell me that i have 100 KVA 3 phase generator so by
thumb rule 100*1.4 = 144 amps
and generaly we can operate at 80% load...so it will 144*0.8
=112 amps....
so now i m confused about single phase load.....if we use
that generator only for single phase the that 112 amps is
total single phase load or i can give 112 amps at red 112
amps at yellow and 112 amps at blue....
i mean that total single phase load that 100 KVA generator
will take is 112+112+112=336 amp ??
Answer Posted / k.prakashchandra
Current in each phase 112 A ,ph voltage say 230 V. Then
apparent power in each phase is about 26 KVA .Sum = 78 KVA
which is almost the permissible load on the gen. If you add
phase currents ,the resultant is zero as they are vector
quantities . You can have a load of 112A in each phase .
Is This Answer Correct ? | 0 Yes | 3 No |
Post New Answer View All Answers
internally connection of photvoltic module
Can anybody post questions asked in Engineers India Limited Interview? Thanks in advance.
why we use single core 630mm2 cable for transformer secondary side
Which thing is maximum in RLC circuit at resonance a)power consumption b)inductive current c)capacitive voltage
What is shutdown of electrical sub station?
What is the actual calculation for transformer short circuit test?.
What are unstable systems?
what is the difference b/w ATS and HTS?
in parallel operation of power transformer why the distance between power transformer and capacitor bank feeder is necessary to know
There is any especial requirement for motor to drive through with VFD?
is it possible to say motor horsepower number without seeing name plate(when name plate damaged)
I have 440v power coming to facility,( not being used ) can I buy large generator, (gas) to sell power back to electrical co.
if we give 60 hz single phase supply to the transformer used in europe , than what will happen
What is the suitable transmission voltage?
how to calculate singlephase motor efficiency?