Difference between directional earth fault and
non-directional earth fault
Answer Posted / jerry smith
Directional Earth Fault detection is used to isolate a
fault, when using more than one source of power input.
Current Transformers are used to verify the net sum of
current as zero between any two sources of power. If there
is a fault, the breaker between the power sources is
OPENED. The protection logic will then see if the fault has
cleared. If the fault has cleared, the fault is on the side
with ungrounded power source, and will protection logic
will trip the ungrounded power supply. Conversely if the
fault continues to flow after the bus tie is OPEN, then the
fault is on the side of the grounded power supply, and the
grounded power supply will be tripped.
Non-directional Earth Fault would be a simple fault
detection, as located on a generator neutral.
Is This Answer Correct ? | 2 Yes | 4 No |
Post New Answer View All Answers
What is surging in a centrifugal compressor ? How it occur's ? How is antisurging done ?
what is the basic use of power plant in equipment
why do you consider yourself a suitable candidate for this position
How to calculate power press toneage
Qatar Fertiliser Company (QAFCO) Shortlisted me for interview (got the intel from my source) for Field Operator- Utilities post. Please let me know what kind of questions they asked? ... this position requires 5 years of experience in Power Plant and background Diploma in Electrical/ Mech. ... my Background is Electrical and I am a sub Assistant Engineer (Operation) at a private HFO based Power plant... PS: Please Let me know what preparation should I take to obtain the Interview which will be take place In Bangladesh soon
some one can tell me how residual type excitation is provided through transformers to an AC generator without any battery or PMG&excitor
How do you consider that you can improve and what assistance do you need to achieve this
operation
im try to calculating seawater flow required for SW-FGD system. I need a guide, equation or method to do it, can some one help me! Thanks very much
what is the difference between compensated & normal drum level in boiler drum?
what's the moog valve
can dp type level transmitter work in under vaccum condition
how to differentiate between "ALL fuel lost" and "All Fuel Lost" in Boiler MFT condition?
can u please tell me how to calculate the concrete quantity for a under reamed pile? r=300mm,depth=3m for a cylinder and for bulb l=.750mm,width=.525
What is difference between secondary Air & Tertiary Air and Their use.?