I have 2 transformers in two different plants, both are
without OLTC but i am facing problem of voltage fluctuation
at LV side from only one transformer.
i have to change its taps manually twice in a day.
Another transformer delivering voltage is ok.
Please guide me about the problem
Answer Posted / 7anoter4
Voltage fluctuation it means voltage drop. It could be a
lot of factors producing big voltage drop.
The voltage drop in transformer -transformer size does not
fit the load and then at load peak the voltage drops under
the permissible limit and in less-or no load-the voltage
raises up to the secondary EMF [no-load voltage]- mainly if
there are many motor starts per hours.
If the supply-medium voltage-is variable-medium voltage
cable too small.
If the feeder from transformer to switchgear is undersized
the main voltage drop could be here.
A complete analysis could find the cause.
| Is This Answer Correct ? | 1 Yes | 1 No |
Post New Answer View All Answers
WHAT IS DIFFERENCE BETWEEN CAPACITOR AND CAPACITANCE?
Define pole pitch?
Differentiate between magnetic field and magnetic flux?
how can we make cable shedule for controll wiring ? which details must be required for it.?
What is an Air COmpressor
why we are using earth pit in sub stations.?
how to do the ductor test?
What is diversity factor in electric installations?
What is the procedure/activities to be taken to inject the current more than 2000A by using 2000A Loading Transformer?
I am going to appear RRB Sr. Section Engineer Exam, Electrical. Can you send me previous year questions of RRB Electrical engineer. specially Section Engineer questions. my email id is likerahulworld@gmail.com
can any one know is sbi interview based on merit or based on roll number
Sir,In our company there are 3 caterpillar make(capacity:(1) 3.3KV,2.5MW(2)3.3KV,2.5MW & (3)3.3KV,1.9MW) & 1 deutz make (capacity:11KV,3.8MW)gas engines utilised,all are running in paralell. There are three transformer utilised,(1) 6.25MVA,3.3KV/22KV,Impedence voltage:6.7% used for two generator,both are 2.5MW(2)5.5MVA,3.3KV/22KV,Impedence voltage:7.2% used for one generator of 2.5MW & (3) 5.5MVA,11KV/22KV,Impedence voltage:7.8% used for one generator of 2.5MW.all generator breakers capacity of 1250Amps. Sir,I want the details of fault level calculation of generator,transformer individually & for whole system. If you require any information from me.feel free for contact me sir.pl.send the answer of my question as the earliest as possible.
How to apply 'c' license and also explain what is difference between 'c' and 'b'license.i am also working in one of the private company.i have finished my diploma in 2014 .i have already finished in ITI electrician course.....
What is a commutator?
What is the main cause of magnetism?