I have 2 transformers in two different plants, both are
without OLTC but i am facing problem of voltage fluctuation
at LV side from only one transformer.
i have to change its taps manually twice in a day.
Another transformer delivering voltage is ok.
Please guide me about the problem
Answer Posted / 7anoter4
Voltage fluctuation it means voltage drop. It could be a
lot of factors producing big voltage drop.
The voltage drop in transformer -transformer size does not
fit the load and then at load peak the voltage drops under
the permissible limit and in less-or no load-the voltage
raises up to the secondary EMF [no-load voltage]- mainly if
there are many motor starts per hours.
If the supply-medium voltage-is variable-medium voltage
cable too small.
If the feeder from transformer to switchgear is undersized
the main voltage drop could be here.
A complete analysis could find the cause.
Is This Answer Correct ? | 1 Yes | 1 No |
Post New Answer View All Answers
oil cooled transformer
I need to connect a synchronous generator to the grid using automatic synchronization and two circuit breakers (one for synchronization, one for end connection to the grid), how to determinate the required diameter of the cables?
What will happen if the d.c. Machine is operated below rated speed?
If a shunt Dynamo has induced emf 100V and 0.4 ohm resistance and battery of accumulator of open circuit emf 110V and 0.5 Ohm resistance are in parallel what is common terminal potential difference?
What type of a DC motor would you use for a lift?
IF HT CAPACITOR IN ON POSITION IS THERE ANY LOSSES I.S I SQURE OCCURS IN THE SYSTEM
What is real time power factor control panel(RTPFC)?
which are the criterias needed to select the kind of neutral earthing(solid earthing,resistance earthing,etc.) at various voltage levels in electrical distribution?
how to calculate the surge level of surge suppressors related to the SF6 cicuit breakers?
What is the feedback in the control system?
what is the voltage between earth & neutral in 3 phase electrical connection.
why in an industry; machine having rated 200 h.p stopped after power factor is maintained above 0.97 lag by control panel in view-of energy saving
state types of reflectors in illumination engg. ???????
How we can change the direction of rotation of Induction motor? Prove it using graphical
How to calculate capacitor bank size at a load 800kVA.