Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...


Dear all... I have 1 0-400 duplex type RTD, I connected the
A side to the temperature indicator and B side to the PLC
panel, but when I have observed then found that The PLC side
temp has the variation. and it was distub to other RTD temp
also. so what can I do.pls help me

Answer Posted / carl_ellis

An offset in readings from separate RTD's can indicate
- a difference in calibration of the analog input devices
- a bad RTD element, one that has drifted out of spec
- a common ground issue with ground loops between the analog
input devices

An RTD is supposed to be ungrounded and the two RTD's in a
duplex element are supposed to be electrically isolated from
one another, so it is unlikely the ground loop is unlikely
unless poor wiring of the extension wire or head wiring has
created a connection to ground.

If you're complaining about a small difference of the
indicated temperatures, then get out your cal gear and cal
the inputs.

To check for a bad RTD, I'd take an ohmmeter and see if any
leg on the A side has any connection to the B side by
disconnecting the wiring from each analog input and check
the resistance. If there's a low resistance, it indicates
some connection from A to B. If the extension wires are
then disconnected and the resistance is checked on the RTD
lead wires and the resistance remains, then it's a bad RTD.
If the resistance goes high (open circuit) then the
extension wire is shorting or making a low resistance
connection somewhere.

Carl Ellis
Measure First

Is This Answer Correct ?    1 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is the use of temperature compensation?

2015


can u plz send me technical questions asked in SCHNEIDER ELECTRICAL technical paper?

4732


Do you have reference list?

1844


How to convert mmWc(mili meter water colam) to tph(ton per hour)?

987


OBJECTIVE TYPE QUESTIONS OF ANALYTICAL INSTRUMENTATION

10717


TEMPERATURE VARIATION FOR FREQUENTLY.

2052


Explain bernoulli’s theorem. State its application.

1196


how many maximum enter 2mm Dia solid cylindrical pipe into 8mm Dia hollow cylindrical pipe. give answer with calculation.

2048


PT RTD Range: -200 to 500 degree celsius If I configured in DCS Lower range and Upper range . In face plate it shows red colour due to overa range how was the characteristics look If the temperature is more than operating range. how was the characteristics look . whether its in Resistance vs Temperature curve is Linear or Non linear

1962


How to Calibrate Ultrasonic flow Transmitter in Field

1274


i need some objective type questions in instrumentation

4904


hiii.... can any one provide me previous years question paper of hindustan petroleum for instrumentation engineering???

1986


what is a good line as ic engineer as maintenance ,oc, project, calibration ,validation engineer?

1991


please tell me what is a light up procedure of Cfbc boiler and what it's axuillaries of cfbc boiler?

8672


How ejector(or)evactor air pump is working in thermal power plant?

6621