Diff between Earthed & Unearthed cable ?
Answer Posted / mds.1490@gmail.com
n 3phase earthed system, phase to earth voltage is 1.732
times less than phase to phase
voltage. Therefore voltage stress on cable to armor is 1.732
times less than voltage stress
between conductor to conductor. Whereas in unearthed system,
(if system neutral is not
grounded) phase to ground voltage can be equal to phase to
phase voltage. In such case the
insulation level of conductor to armor should be equal to
insulation level of conductor to
conductor.
For example for a 6.6kV ungrounded system, 6.6kV/6.6kV (UE)
class cable has to be used while 6.6kV/3.8kV (E) class
cables are adequate for solidly earthed systems. The
UE-class cable is
naturally costlier than the earthed class of cable.
Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
Saving in copper achieved by converting a 2 winding transformer in to an auto transformer is determined by A voltage transformation ratio B load on secondary C quality of core material D size of transformer core
Define pole pitch?
How harmonic block test are conducted on relays ( Siemens,Areva ect )power transformer using omicron kit?
what is the excess air in furnace
Why the arms of delta in a delta-wye power transmission system are kept constant??
What is ignition module of a CAT Gas Genset G-3508 Engine, Alternator SR4B Series. HOw its checked for correct functioning.Is it repiarable or replacable?
how to calculate insulation level of transformer?
what causes contact chatter when there is no demand on the air conditioning unit?
what is Fault level? why it is calculated? how will u decide same for our plant?
how to determine the inrush current of a transformer
what is errection pcbs?
when we decide to use soft starter drive or vfd drive in mcc to operate apump?
when it is possible kvrah lead & fundamental kwh be equal in electonic trivector meters (3 ph)
I have 2500KVA transformer delta/star,13.8KV/380V provided with LV 4000A breaker. Already I have 2300KW motor feeder with a full load 90%. Is it possible to connect another 1600A from that breaker? If so how the calculation is done?
hi if anybody got model questions for cpcl Grade'A' electrical engineer position.send it to my mail please krishkumar22@gmail.com