how much current capacity of 300 sq. mm cable (4 core
aluminium) and 150 sq. mm cable ( 4 core aluminium)
Answer Posted / 7anoter4
It depends on lot of factors. The duration of the load:
short-time[as in short-circuit case],continuous load,
intermittent load. It depends on also on ambient type [air,
underground-direct laid or in concreted duct],on thermal
resistivity of the ambient [if it is in underground],on
ambient temperature, on insulation type[bare, pvc, xlpe,
epr etc.] and other factors.
Let's say in short-circuit case for 1 sec 300 square mm
aluminum conductor pvc insulated. Permissible temperature
[for PVC short-time]= 150oC.Ambient air 30oC.
Ipermissible=27 kA[27000 A].
For the same cable in open air 30oC[NEC Table 310.15(B)
(17)] continuous load [75 oC]600 MCM=300 sqr.mm permissible
545 A
Is This Answer Correct ? | 1 Yes | 3 No |
Post New Answer View All Answers
What is the permissible limit of shaft voltage for 6.6 KV motors ? Why? Is there any standard is available?
Are Refrigerators & Deep Freezers the Inductive load ? How to calculate the Power Factor & hence the Output Power for them ?
What are high pass filter and low pass filter? and What are the flowmeter ?
what is the affect of earth's magnetic field on the frequency used in aircraft???
Is a contactor (or master relay) required between incoming lines and a VFD? The question goes to safety. If a contactor were used before the VFD and an e-stop engaged then the motor will coast to a stop (i.e. VFD loses power) instead of stopping much faster if the VFD braking fucntion were used. It would make more sense to keep power on the VFD.
What is the difference between single point and double point bonding. please kindly detail about bonding of cables.
hai friends i have BSNL JTO exam on next month so if any body have model question paper or give preparation tips to my mail id kumar4486@yahoo.co.in this will helpfull for my future .plz & thank u by kumar
In constant power region of 3-phase IM torque-speed characteristics, if frequency increases flux A does not alter B decreases C increases D none of above
How to size Air Circuit breaker (ACB)? What is the most important factors?
Why in metering Ct for ammeters ct secondary side is grounded for each Ct but not in case of CBCT (Core balance current transformer)..kindly some1 highlights the reason..is it because net flux is zero?
How does zener phenomenon differ from avalanche breakdown?
234 MVA Generator 3 phase Short circuit current Values required? Gen set Rating-234 MVA, Gen Voltage-18kv, PF;0.8, Xdv:23.5 %, Transformer Rating-18/380KV, 680MVA,Yndd1 two winding, Step up TR, ZT:35.50 %,X/R 4.33 Gen CB Position, CB open ,Disconnected open, Generator Running Voltage 18 Kv, Bi mistakes generator side earth switch Closed during that time short circuit current level in 3 Phase required, and how to test on site 234MVA Generator Short circuit current,
How many methods use the load flow solution?
How could I get a certificate of competency as Electrical Supervisor? I have completed By BTech in Electrical this year(2012) for VJTI Mumbai Maharashtra. Is it compulsory to be produced while joining?
how can service sitting be setted for MCCB?Example for sittings IR (CURRENT RATING),IS(CURRENT STARTING) I O (current operating)?