if temperature transmitter is showing wran. sensor 2 fail how can you remove from the transmitter display m/n.3144p rosemount
Answer Posted / carl_ellis
It is very likely that the original question has not
correctly copied the error code.
"wran sensor 2" is most likely "WARN SENSOR 2"
It is impossible to search electronic pdf documents if the
error message is spelled incorrectly.
This is why employers look for things like misspellings in
documents submitted by job candidates, it shows whether the
candidate pays attention to details.
Here is what the 3144P manual says about the WARN error
message:
"The transmitter is still operating, but something is not
correct. Possible causes of this condition
include, but are not limited to, an out-of-range sensor, a
fixed loop, or an open sensor condition. In the
case of a Sensor 2 failure with Hot Backup enabled, the
Process Variable line displays “WARN,” and the
Process Variable Unit line alternates between “SNSR 2”
and “RANGE.” "
Carl Ellis
Measure First
Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
I faced several time siemens ps2 positioner automatically getting Chang in it's set point direction after auto calibration So is there any causes biside this or any permissives ?
what is the procedure of O2 sensor(ABB) calibration?
why we use 3 wire rtd direct wiring for temperature measurement instead of temperature transmitter like bearing temperature
How to change dcs card in online. (Dsc is maxdna)
Where is wet leg is used?
Yokogawa CENTUMVP R6.09 unable to download to Engineering Station with ExaOPC R3.75
The issue is when I try to download the common project section to the Engineering Station (STN) from the HIS in System View, it is unable to connect. The error displayed is:
WARNING: Could not connect to equalize destination. (7001)
Retrying. Number of retries = 0/1
ERROR: LdXopsLoadMain: connect error 10060
ERROR: Processing terminated due to connection error. (7002)
Equalization end with errors. STN0149
---- ERROR = 2 WARNING = 1 ----
Background:
>Updated the ExaOPC software on the STN from 3.60 to 3.75
>STN operating system is Windows Server 2008 R2
>HIS operating system is Windows Server 2016 Stanard
Solutions attempted include:
>Ensuring all IP addresses are correct and all networked devices can be pinged.
>The ability to ping a device using its host name from another device (
What is wet leg condition and why is it used?
what is use of communication wire in multipare cable(oil and gas field), why this communication wire not used in single pair cable?
1. what is modbus cable? 2. what kind of communication we are using for the interface of DCS, ESD and Third party cabinets? 3. What is serial communication and peer to peer communication?
why we us isolation barrier in hazardous area how it works to protect the area and please clarify its current flow.
Explain the mechanism behind the turbine meter.
Which Signal hart communicator work? If there any signal change when hart connect while transmitter in line ?
What is standard procedure of manual mapping in Radar type level transmitter?
send me last 5 years questions asked in rrb chennai, for section engineer
How to calibration a control valve?