difference between shunt coil and tripping coil
Answer Posted / andrea vanni
shunt coil is not good for safety purpose use, but only for normal operation (usually to close the brk).
For safety purpose, it is necessary to apply the "fail safe" logic, then an undervoltage release coil shall be used.
usually on MV switchgear we have one closing coil shunt type, and two opening coils undervoltage release operated: one for trip commands, one for normal opening.
Is This Answer Correct ? | 2 Yes | 3 No |
Post New Answer View All Answers
i have gear oil pump with single phase motor.some time its motor starts running in reverse direction rather than forward direction...whats the reason behind this issue. 1- either capacitor is week? 2- or winding is week?
What are the applications of the electric motors?
block diagram of 2 ups system connected in hot stand by mode?
what are the standard IR values should be of R-E, Y-E, B-E, R-Y, Y-B, B-R of VCB in closed condition and in open condition for 500KVA & 1000KVA transformers. and what is the acceptable range when tested by 5000V megger.
Post possible questions for Power Factor Panel FAT / SAT
how to know the diffrential relay setting of 06mva step- down (delta-star)transformer?
What is the difference between circuit breaker and isolator
what is the role of energy meter in distribution system ?
where rlc series ckt used?
How can I model an open-delta ground transformer for a network supplied by 4 unit GTG and power transformer in ETAP?
what sort of general awareness questions are asked in o.n.g.c entrance exam?????????????????
what is the difference between RMS & TRUE RMS VOLTAGE
Graphs of measuring power and speed on dc motor
132/66kv sub-station procation ?
Can a generator runs after getting 1st stator earth fault.