What is the difference between a Vacuum Circuit Breaker and
a Load Break Switch?
Answer Posted / amin
All of the above posts stating that the function is the
same are technically WRONG.
A Load Break Switch is designed to ONLY interrupt a circuit
under "normal" operating conditions. They are NOT or
intended designed to interrupt fault current! Even if
designed to automatically open (motorized), they must have
fuses in the circuit to interrupt the fault first and the
let-through current of the fuses must be coordinated to
stay below the load interrupt rating of the LBS.
A circuit breaker is designed to interrupt fault current,
and acts as an alternative to fuses. So a CB is both a LBS
and a Fault Interrupter.
Is This Answer Correct ? | 3 Yes | 2 No |
Post New Answer View All Answers
Why increase in current leads to increase in conductor temperature?
Why the earth to phase voltage is high 250 compare to other two phases
WHAT IS IM (INDEX OF MOUNTING )IN MOTORS
we have two motors 1250kW,6.6kV to be coupled on the same shaft ,so please provide assistance for their synchronisation.
for opening electrical shop, tips needed.
wat is the first thing dat is needed, 2 lay a cable in some area??
Should power factor be low or high?
how much excitation voltage required to generate 1mw power?
tell me about roaster switch .& what is the function in transmission & distribution?
When we use 3 terminal resistor?
1. transformer design formula ? 2. how to calculate the primary turns and secondry turns ? 3. core types ? 4. how to find the primary current and secondry current ? 5. how to calculate the stacking factor ? 6. range of fulx density ?
what are the possible reaons & remedies if resistance of NGR getting heat up
can i connect the two phases of scott connected transformer,if not why?
how to select rating of HT Panel
why the projects getting loss?