Answer Posted / carl_ellis
Static pressure is the line pressure (gauge or absolute) at
the high port when measuring a differential pressure.
Static pressure affects the DP measurement (with current
technologies) at pressures greater than 1,000 psig (69barg).
Some commercial DP transmitters (Honeywell and Yokogawa)
use an absolute pressure sensor sensing the high side port
pressure which is used to correct for static pressure error
when static pressure is greater than 1,000 psig.
A separate calculation for static pressure error is provided
for DP transmitters (by the major vendors) as part of a
total uncertainty calculation.
Multivariable transmitters (a DP transmitter with a
temperature sensor and an absolute static pressure sensor)
use the same technique of measuring (absolute) static line
pressure for calculating inferred mass flow for gases.
Carl Ellis
Measure First
Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
Which are all the commonly used Bordon tubes in the pressure gauges. Do any one use ASTM A 312 tubes for this purpose?
what are procedure of sox-nox calibration
How to Calibrate Temperature Switch in field
What is the differerence between hysterisis and linearity.
the whole paper was based on Transducers..questions like define repeatability, error,accuracy,precision..den there were many q. on the conversion of Pa to mmHg and other units.. also..der wer few Q. on some level sensors(with diagram)
what different types of problems do occur while doing instrumentation commisioning and how to solve them? please explain in detail
pls give me presant awerness quistion and answer in my emailid.
how works encoder in plc
what is wave length were using ?
Name different parts of a pressure gauge.
How will you calibrate PID controller? explain with example.
Difference between ultra sonic flow meter
What is difference of fanuc alpha series 16i and 18i controller.also what is differnce betn TC and MC controller
a flow transmitter [range-0-400mbar] connected in process line. please explain me how to calibrate the flow transmitter , & how to do static error
give me all the details about the interview and which type of question being asked