why transformer impedance measure in % (percentage)
Answer Posted / 7anoter4
Usually group of transformers presents the same short-
circuit reactance in %
For instance, for S[ rated power] up to 2500 [to 3000] kVA
the percent reactance will be vk%=4-8. Ohmically calculated
reactance will be V^2/S*vk%/100 [ V=rated voltage].
For V=10 kV and vk%=6 for S=500 kVA Xk=10^2/0.5*6/100=12
ohm
For V=6 kV and vk%=6 for S=3000 kVA Xk=6^2/3*6/100=0.72 ohm
As one could see it is more convenient to consider only
vk% instead of ohmic reactance
Is This Answer Correct ? | 0 Yes | 1 No |
Post New Answer View All Answers
Ac generato how produce power I need for camplet defination
Please tell me the formulaes while designing a substation for power Calculations in designing a 33 KV Substation?????
Explain what are inter-poles and why they are required in a dc machine.
how we find transformer capacity by ohm
What is the rating of a circuit breaker needed for 300 kv load in 33KV supply line of 33/415 transformer ? Whether 800/1200 amp vaccum circuit breaker can perform for a 33 KV line in input in 415 volt in output of the transformer ?
what is a synchronizing lamp ?
Purpose of providing neutral isolation panel for parallel operation of diesel generator
WHAT IS DEAD END IN PROTECTION?
define the non synchoronism of synchoronous machine in general g or m??
how to control the speed to switched reluctance motor
what happens to the water pump if ground water level is slowly decreasing?our water pump is varying from no-load full-load due to this problem
What is nichols chart?
block diagram of 2 ups system connected in hot stand by mode?
The specific heats of the gas at constant pressure and constant volume are respectively 1.0 kJ/kg K and 0.72 kJ/kg K; the value of R for the gas is
What is the formulae of Megger value for a A.C.Motor