What are the point of a single core cable to be earthed?
Answer Posted / 7anoter4
The grounded point of a cable shield[or screen] could be :
1)at the supply side-usually is not necessary since the
supply side is enclosed
2)at the far end-is better for receiver security.
3)if the built-up voltage-due to induction produced from
the current flowing in the main conductor-is elevated [more
than 25 V usually limited]then a middle point grounded will
reduce this voltage to a half.
4)Both ends-if the middle point it will not reduce enough
the built-up voltage.
However, the circulating current will produce a
supplementary heating of the main conductor and then a
derating factor should be introduced.
There are also other means to overcome this by cross-
bonding the shield and even the main conductor, also.
Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
What is bridge rectifier and explain with details
Why we use ups battery and dsdb battery in thermal power plant
what is the difference between changer, converter and transformer?
How to calculate the multiplying factor for energy meter with ct ratio given
How does PLC work for sychronising of Two or more DG sets?
How Load Factor, Demand Factor, Diversity Factor etc best applied in designing an electrical circuit? Is it allowed to consider these factors in each and every panel in an electrical distribution system? Can any body suggest a good book for reference?
what is strip power factor?
what happens if earth of 33kv cable is not connected to earthing pits? please send this query's answer to ngrm.sudha249@gmail.com
What is the classification of hydro projects based on installed capacity?
What happen to generator if i have unbalanced load?
What is the formula for calculating no-load current?
For electrical designers what are the standard should know? i want learn about this standards. how to get information/reference. anybody help in this regards please.
hi everybody how to design string combiner box (scb) internal parameters like bus bar and spd (surge protection device and fuse which place to set that,and also bus bar one particular cross sectional how much heat generated and how much power loss tell me Clearly and briefly
How is efficiency of DG set calculated? At many places I found the efficiency to be mentioned in percentage. But at some other places I found kWH/ litres. I want to know how dimensionless percentage value is arrived at?
any earth foult trip the relay but in welding time not trip by earth foult