how we can calculate the transformer size.

Answer Posted / satya mahesh

load factor(LF) and utilization factor(UF) will play a
major role in transformer selection.
Connected load-4810
Maximum demand in a month-1582 Amps
Average load which will be the average of running loads
came in a month-1173 Amps
LF=average load/max demand
=1173/1582
=0.74
UF=No.of hours running Equip/total hours in a month
=(30*20)/(30*24)
=600/720
=0.83
Transformer size= Connected load X LF X UF
=4810 X 0.74 X 0.83
=2954 Amps
for 2954 Amps 2500 KVA(3484 Amps) transformer was suitable
in continution to the future loads also.

Is This Answer Correct ?    2 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Explain bypass capacitor?

650


What are the major reasons for balancing hydro-thermal mix?

682


how to minimize earth resistance upto 2Ω, if the resistance is 6 Ω ?

1451


I need HT sphere gap calibration table. Can any body help me.

1526


how can decide the current rating of oltc

1861






why the projects getting loss?

1431


WHAT IS THE TOTAL POWER GENERATION IN CHHATTISGARH?

1477


what is frequency response?

649


Sate maximum power transfer theorem?

701


3Cx240 & 3Cx300 sqmm Al. cable from lv side. What is the calculation for this cable??

896


who many types of fire explane with exmple

1738


In synchronization circuit what is the function of Interposing voltage transformer(IVT)and Reverse voltage transformer(RVT)

10967


What is the count of hvdc transmission lines in india?

626


how to caculate cable size for diff types of loads? if anyone know the calculating procedure please tell me

961


How to design a Unit auxiliary transformer for a power house having a unit of 65 MW and Generating voltage of 11 KV and Secondary voltage of 433V

1664