why we take 4 to 20 mA as out put of every instrument like
pressure transmittre ?why we cant take 0 to 20mA as output?
Answer Posted / vinoth s
If we use 0 to 20ma, then 0 will be the minimum value and 20
will be maximum value.. In case if there is any problem in
the transmitter or in the cables, we get the value 0 but we
think it as a minimum value..we cant able to know that
there is problem in transmitter.. In order to overcome these
constraints, we went for LIVE ZERO concept as 4ma.
0 ma will be consider as DEAD ZERO.
Is This Answer Correct ? | 24 Yes | 0 No |
Post New Answer View All Answers
Which type of pressure can be measured by primary elements?
Explain bernoulli’s theorem. State its application.
diff between neutral ,ground,phase , earthing and shielding?
what is thermo coupler and how it works
what is cems analyzer explain with principle and drawing ?
what is o2 analyzer and how it measured ,what is the role of this analyzer in cfbc boiler...
Lux meter is the measuring device to measure the lux level of lighting fixture. in industrial sector two types of lighting fixture is being used as street lighting purpose 1. HPSV (Sodium) and 2. HPMV (Mercury). HPMV having white light which is an combination of red, blue and yellow colour, while HPSV haivng Yellow lighting. in HPSV red & blue colour will be absent. during measurement of the lux level of HPSV and HPMV fixture. 1. Lux meter can measure the actual lux level of both fixture? 2. or it will show false reading for HPSV fixture light as it has only yellow light present. please give me answer
ORP sensor working principle?
WHAT IS THE CAM POSITION IN CONTROL VALVE POSITIONER ? WHY IT IS USED?
How d.p. Transmitter can be applied to open tank?
If i have 4 Allen Bradely make RS logix 5000 PLC and for viewing that we are using 4 RS view SCADA for 4 different packages. Now, I will want to view two packages on only one SCADA. Then how i will do it?
in which principle pressure tx,level tx ,flow tx,temp tx ,control valve works?
What is wet leg condition and why is it used?
Draw a great bridge circuit.
how many pulses are required by a ac induction servo motor of 4 poles with 50 Hz frequency to rotate by 1 degree?