What will be the effect of in HT XLPE 220 KV
cable when one side of the Armour/cable ends are not
grounded. Will there is difference between 3-phase voltages?
like: if
A. Both End of Cable grounded Phase Voltages:- V1=219 KV,
v2=220 Kv, v3=220 KV.
B. One End is grounded other is not: than Impact on Phase
Voltages:- V1= KV, v2= Kv, v3= KV. Remain same or
unchanged??
Answer Posted / k.prakashchandra
You have measured voltages with the help of PTs located near
the earthed cable ends . As there is a slight difference in
capacitances of the three cables to the Armour(probably due
to unequal lengths) and impedance of the PT is higher than
that of capacitance of the cable ,the neutral is decided by
the capacitances.There is no difference in actual voltages
but there will be a slight difference in measured voltages
Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
CAN ANYBODY PLEASE TELL ME HOW TO DESIGN A SERIES REACTOR FOR LIMITING SHORT CIRCUIT FAULT CURRENT??
Could you measure voltage in series?
what is (+) and (-) in generator field detector stand for?
what is the minimum recommended leakage current of an earthed cable connected to the body or skid of an alternator
how to calculate the mesh earth network resistance in such substation, is there any recommended resistance values with references , thanks!
previous year paper of ntpc bhel for degree in electrical enng
What is the criteria that generally follow by distribution licenses to fix contact demand of their industrial customers?
Explain Creepage Distance of Insulator
HOW TO TEST A LIGHTENING ARREST ER ?
I completed my BE EEE degree 2006 .... which license should i apply .... ?????
Please define ampere?
What is line resistance of cable & how it can be measured ?
How to decide no. of Step and Kvar for APFC Panel 40 kvar MD: 33.12 KVA Avg pf : 0.8540
On what principle electric motor works?
Explain M Var? Which types of problem occurs when reactive power increase at the time of full load of plant and at the time of synchronize of plant?