Answer Posted / warren holden
Yes, a control valve can be used without a positioner.
Some of the previous responses contain correct information
about certain elements of what a positioner actually does
however they do not address the fundamental issue from a
control perspective.
The positioner on control valve is essentially a cascade
(inner) loop acting as a high gain proportional controller
within the external (outer or master) loop (Shinskey, G.F.
1988). The positioner will be beneficial if its response
time constant is faster than the master loop element(s)
i.e. in the case of a temperature control (master) loop the
control valve positioner dynamics will undoubtedly be
faster than the temperature measurement change dynamics
(this being a fundamental requirement of cascade control).
However, the control valve positioner is of no use, and
actually a hindrance, on fast acting master loops i.e. flow
control with fast change dynamics. Hence control valve
positioners are often not used on flow control loops where
the outer (master) loop flow measurement and associated
controller can handle the control valve positioning quite
well themselves.
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
What happen if we install my pressure transmitter below the elevation of pipe in natural gas service?
What is 3 element control system
we are using centum vp as monitoring with Dell precision work station T3600 but some times PC(s) are restarted automatically . how we can solve this problem? thanks
What is hp & mp seperator .& what is its working principle ?
what is the difference between active & reactive power?
Can anybody tell me how to select the size of earthing cable for DCS & PLC system.Please tell me any relevant answer here or mail it to me.
what is the protection system in solar turbine compressor
how to calculate control valve bonnet size?? or how to select its material?
how to control pid
Which type of pressure can be measured by these elements?
Manipulation of dead wt. tester double piston type.
What is the difference between modbus,fieldbus & profibus
i have used level transmitter in starch cooking preparation tank. tank total height 2mtr.sometime LT display shows some error value when tank is fully empty and diaphragm side i already checked okay no problem in diaphragm area. field cable checked 24volt and mA shows correct value while tank empty mA is 4mA. 4mA i needed that 0% but display showing 10% or 15% percentage values are varying continously please give any good solution for me.....
Valve positioner and actuators in detail.
In turbine what does term CDP, NI, NH, HSSOC means.