Answer Posted / shyam kishor
Merz-Price protection is the method used for protection of alternators. it is a most common system used for the protection of stator winding faults employs circulating current principle. in this scheme of protection,current at the two ends of the protected section are compared. under normal operating conditions,these currents are equal but may become unequal on the occurrence of a fault in the protection section. the difference of the currents under fault condition is arranged to pass through the operating coil of the relay. the relay then closes its contacts to isolate protected section from the system.(Ref. book on power system v.k mehta and rohit mehta)
Is This Answer Correct ? | 65 Yes | 8 No |
Post New Answer View All Answers
Why HT 11 KV Slipring Motors are connected in star ?
What do you mean by per capita requirement of electrical energy in india
why we have to particulary use ACB for below ratings,even available of MCB,MCCB with that range ?
When calculating the speed of a rotor required for a particular frequency of synchronous generator we use the equation 60f/p Is this p is the number of pole pairs of rotor & do we consider the number of pole pairs in the stator is 1?
How does a digital electronic meter work??????
can we use engine degreaser for electrical motors?
What is bode plot?
What is excitation in case of dc motor?
Why derating factor os applied on Cables?
How to calculate the fuel consumption for 600kva DG genset which connecting with 25%load?
Is it possible to connect a safety device in to parallel?
How to calculate MCB Breaking capacity.
In what cases (circumstances)we should apply P controller, PD controller, PI controller & PID controller ?
how does WTI work ?
How delta connection in the primary of distribution transformer reduces harmonics?how delta connections reduces harmonics?Please answer me...Hope that question is correct.