I have 1500KVA transformer ,How much Maximum KW Load is
allowed?
Answer Posted / ashutosh + mukesh
In distribution system, generally the p.f. taken in account
is 0.8
Beacuse our transformer is 1500KVA.
SO = 0.8
FROM FORMULA:- KW = KVA*P.F.
so KW = 1500*0.8
KW = 1200
So our transformer upto 100% load= 1200KW
Beacuse we take maximum 80% load on Transformer for safety
so: =1200* 80/100
=960kw
| Is This Answer Correct ? | 61 Yes | 7 No |
Post New Answer View All Answers
how the CT and PT is connected in the circuit during testing of transformer explain with diagram
what percent do you derate your copper wire when you change from copper buss to copper wire
hi there i am highly enthusiastic about discussing electrical concepts , and hence i wud lyk to invit al do intrested to join me at gtalk and hav a dscussun of the concepts , ad me as a freind . my email id is rakesh.2k99@gmail.com
sir plz send some previous year questions of jspl.
Differentiate between ideal and non ideal current sources?
What if high voltage side circuit breaker of a ehv transformer instead of lvcb? Kindly elaborate.
If more than rated DC voltage appears across trip coil of the breaker, what will happen? e.g. in 110V DC circuit system, if voltage across battery terminal showing 121 V
What happens if we connect a single phase energy meter in reverse polarity.
What is the function of a neutral reactor.
what is the difference betweem star connected motor & delta connected motor?
Dg pf .71 i am improve pf 0.80 what capacitor connected in dg how?
what is the basic need of domestic loads 1- voltage 2- current
How can maintain our H.T. motors used in cement plant. please send me procedure.
Why the efficiency of a three-phase induction is the motor is less than that of a three-phase transformer?
What is difference between Sample test and Routine test in safety standard?