I have 1500KVA transformer ,How much Maximum KW Load is
allowed?
Answer Posted / arvi
It is interesting how much wrong answers can be gained with
one simple question. I assume that all people answered are
somehow involved with above mentioned theme. To avoid
problems and cost for you in future I´ll give you few hints.
First of all I want to remaind to everybody that
transformers are normally custom made equipment and to
answer this all transformer data has to be presented. Same
well you can ask how far can you drive with the car having
150kW engine!!!
1. I presume that such big transformer feeding not much
equipmnt stating its elektrical KW. On your engine
nameplate you find mechanical kW on engine axe. It has
nothing to do with engine electrical kW.
2. Transformer load is always calculated in Amps. And that
is information what you can always find on all and every
el.equipment as well as on the nameplate of your
transformer. Simple as that.
3. In normal cases you can not presume how many Amps you
will use as it is depending on the load on your equipment
what is varying in real life quite much. So you or use max
Amps stated on nameplates or expected Amps by your
specialists or you set up the Ampmeter and measure it.
4. Normally you dont want to load your transformer
permanently more than 75% as there are always swiching
processes giving load jumps upto few times more than the
full load of your transformer
5. It is very important to consider permanen distortion
level what your equipment emissing back to transformer and
the distortion level coming from higher voltage side. This
is complicated issue what is quite simple to measure, but
for that you really need specialist.
6. Distortion creators in your network are lighting,
smartequipment, variable speed drives, office technology,
UPS systems etc. If you dont have special converter type
transformer then you have to degrade the allowable load as
much you have the distorting equipment. If you have all the
load distorting for example then you dont want to load your
transformer more than half power only. To be honest then
even less, but its again depending on the type of
distortion.
7. Easiest and cheapest is always to ask specialist giving
you stright and exact answers. Trust me - it always pays
back. In this forum you have had answers from the level of
housewife to secondary school students. They are partly
right but non of them giving you really full answer.
Is This Answer Correct ? | 7 Yes | 8 No |
Post New Answer View All Answers
in an electronic tri vector meter when the current and voltage sequence changes ? what is the effect of phase sequence on recording of meter
In siemens S7-300 PLC, what is function and function block ? What is the difference between them ? When to use function and when to use function block ?
concept of busbar and load dispatching..?
What is the formula to calculate the rating of a three phase miniature circuit breaker
What is the formula for calculating impedance of transformers connected parallel at fault level 50KA?
Who are the manufacturer for Nitrogen based Fire Protectio/explosion prevention for Oil Filled Transformers? India and international both?
How to measure the Harmonic Distortion of UPS ie THD?
How to decide CT & PT ratings for a given transmission line carrying some rated voltage?
Explain cmrr?
What are the essential characteristics of signal flow graphs?
Draw a SLD of DG distribution up to main LT panel?
how can service sitting be setted for MCCB?Example for sittings IR (CURRENT RATING),IS(CURRENT STARTING)IO (current operating)?
what is the max. acceptable leakage current in 33kv bus bar
how is control wiring coding is done in a CRP panel ?
if voltage bt phase & nutral is 38v in a panel board . whats the root cause.