there is a power transformer 66/11kV in delta-delta
connection has 5 feeder coming out from the secondary side.
One of the feeder in it normally loaded (loaded than other
feeder)and this feeder usually trips with double OCR causing
the bank transformer to trip. Now if the load of this feeder
is put on other transformer then that no problems occurs on
that transformer or the load. However normally all the
test(IR, PI, short ckt, open ckt,grounding test and other )
has been conducted for this but evertything transformer.....
I am not geting what is the actual problem...

Answer Posted / parin patel

This thing happened dew to %Z of transformer.lesser the %Z current supplied by transformer will be more.
example:- there are two transformer
transformer 1: 66/11 kv,%Z= 5% ,15 kVA
transformer 2: 66/11 kv,%Z= 7%, 15kVA
If load is constant(same), current supplied by transformer 1 at 11 kv is more than current supplied by transformer 2 at 11 kv.

In your case ,you have to check the value of feeder current when it's supplied by two different transformer.in both case it might be different.

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is the relation between frequency and motor rpm?

1330


what is mean by Digital Logic Meter (DLM)

1859


why normally Generator rating are between 11Kv to 22Kv?

3705


Explain mechanical rotational system?

635


What is the working principle of CFL & T5 tube light & 40W tube light with electronic ballast?

3496






What are the advantages and disadvantages of open loop control system?

654


why magnet has north and south poles only why not east and west and why we are considering as north and south poles? why cant we consider as east and west?

1494


why single CT used in DOL starter power circuit?

2057


How I calculate the ELCB for circuit breakers?

1655


I have a drawing of a wound rotor induction motor for a crane. This crane motor has 5 forward speeds & 5 reverse speed implemented of course with different amount of resistance for each speed setting selected. What has got me scratching around is the fact that 8 of the 10 speed selections switch in uneven (unbalanced) amounts of resistances on each of the 3 connections to the motor's rotor.Can this be possible? I would have assumed this would produce unbalanced rotor currents and therefore vibration in the motor. I would greatly appreciate anyone's comments on this. Many thanks, Confused.

1403


what happens to the water pump if ground water level is slowly decreasing?our water pump is varying from no-load full-load due to this problem

1209


When steam condenses and becomes water at the same temperature, the specific heat for the process in kJ/kg k is

650


What are electric motors?

651


what sort of general awareness questions are asked in o.n.g.c entrance exam?????????????????

4203


full form of electrical?

2290