WE ARE HAVING YOKOGAWA CENTUM CS 3000 DCS, 2 FCS AND 4 HIS "
When the operation Download to HIS message appears:
Equalize start. HIS0163
WARNING: Could not connect to equalize destination. (7001)
Retrying. Number of retries = 0/1
ERROR: LdXopsLoadMain: connect error 10060
ERROR: LdXopsLoadMain: connect error 10060
ERROR: Processing terminated due to connection error. (7002)
Equalization end with errors. HIS0163
---- ERROR = 3 WARNING = 1 ----
Tell me, please, why and how to solve the problem."
Answer Posted / prashanth
thanks mr Jigar Anadkat
Instrument Engineer
IBN RUSHD a SABIC affiliate.
your suggession really helped
actualy firewall was turned on in HIS0163.
I TURNED OFF the fire wall and gave download,then it got
dowloaded successfully.
thank you
Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
What is motion balance principle?
What are the interlocks we have to check during the start up of LP/HP compressor?
I want measure the volumetric flow of gas in waste heat recovery Boiler?Tell me how and which type of instruments required. Plz mail me:naba02222@gmail.com Sam please post the answer .
WHAT ARE THE INSTRUMENTAL DIAGRAMSOF VALVES?
if my flow is 20000 m3/h than which range of DPT i have to use????
How to calibrate an pressure gauge with yantrika test bench?
Do you have reference list?
Explain the working of an electronic level troll.
How servomotor controls throttle valve of TURBINE?
Can please tell mi about SIOS, PRM, SERVER, and what is the diference between PIN LAN, PCS LAN,APC Server, and please send the Doc if possible for referance,mail id patil_amit17@yahoo.com
How to calibrate capillary type level transmitter
Galvanizing.
How an rtd work, and what volts/current goes to a rtd to measure the resistance?
how can be calibrate flow indication transmitter (rosemount) it shows excess milli amps nearly about 24 ma on full scale, but its scale was set on 20ma on full scale..???how can be simiulate..???
What is Positive Calibration and Negative Calibration?