If the neutral wire go pass through the core balance current
transformer? If yes then why? and no then why?
Answer Posted / rajevaibhav
If Current Flowing through the cable is balanced then
output of the CBCT through which the cable is passing is
zero. If you pass the Neutral through the CBCT and if fault
occurs then part of fault current will flow through the
Neutral which will also travel through the CBCT and CBCT
will not produce any output hence Protection will not
operate. Hence Neutral should not be passed through the CBCT
Is This Answer Correct ? | 3 Yes | 4 No |
Post New Answer View All Answers
why the earth is taken minimum in supplying? wather it the proportional factor to getting work any equipment or a power plant?
High voltage test procedure of in swgr board. why should measure millivolt drop on testing time?
How will you justify IR value and Charging voltage of any motor,transformer and Cables.......???? . . . . . . . . Plz tell me any body Baljeet Singh, engineer_89@refiff.com
How will be the single line diagram of series trip HT breaker? how it works?
What is George phenomena to start the synchronus machine?
What do you mean by a phase angel of instrument transformer?
Difference between drift current and diffusion current?
Can double compression glands be used with regular cables?
Draw the single line diagram of the power station?
What is PEC??Applications........
Advantage of LT panel vs HT panel
what is meant by rotating magnetic filed
bsec exam syllabus (mis)
what is the advantages og idmt relay over magnetic relay??
What is the pro & con of having 11kv & 33kv incoming, and what is the adv & disadv. of converting from 11kv to 33kv.